Conventional Photoelectric Smoke Detector

ECO1003 A

The conventional ECO1003A photoelectric smoke detector uses a state-of-the art optical chamber operating on the light scattering principle, combined with an application specific integrated circuit to provide quick and accurate fire detection.

• Low profile design
• Low current draw
• Automatic drift compensation
• Operates on 12 and 24VDC Systems
• Remote alarm test feature
• Easy Maintenance
• Range of detector bases available
• Remote LED Option
Operating Voltage
8 to 30VDC (Nominal 12/24VDC)
Maximum Standby Current
@ 25°C 60μA @ 24VDC
Maximum Permissible Alarm Current
80mA (current limited by control panel)
Temperature Range
-30°C to +70°C
Humidity
0 to 95% Relative Humidity (non condensing
Height
32.5mm (plus 9.5mm for standard base)
Diameter
102mm
Weight
75g (plus 45g for standard base)
Max Wire Gauge for Terminals
0.4mm2 to 2.0mm2
Colour
Approximates to RAL9016
Material
ABS
  • ECO1000B Standard Base
  • ECO1000BREL12L Relay base 12V Latching
  • ECO1000BREL24L Relay base 24V Latching