Manual Call Point isolated

M5A-RP06FF-K013-41

The Honeywell Morley-IAS addressable Manual Call Points are designed to provide a manual alarm interface to Morley IAS´s fire alarm control panel. The flexible release plastic element provides a resettable option by using the provided key. Instalation efficiency, flexibility and compliance with the latest standards are at the heart of the call point range. The unique 'plug n play' concept is designed specifically to reduce installation time by using a terminal block which can be wired during the initial installation cabling with a link to provide continuity for testing. During the commissioning phase, the links are removed and the terminal block is simply inserted into the connector at the back of the unit. No re-termination is required.
  • Unique plug and play installation concept
  • Resettable, unbreakable flexible element
  • Rotary decade address switches
  • Analogue addressable communications
  • Semi-flush and surface mount option
  • Integrated LED
  • Integral loop isolation
  • Specification: EN54-11, EN54-17
  • LPCB Approved

Additional Information
Includes transparent cover PS200.
For surface mounting requires PS031W.

Operating voltage15 ... 30 V DC
DimensionH: 89 mm W: 93 mm D: 27.5 mm (semi-flush) H: 89 mm W: 93 mm D: 59.5 mm (surface mounted) H: 97.5 mm W: 105 mm D: 75.5 (surface mounted & transparent cover)
Weight110 g (Semi-Flush), 160 g (Surface Mount)
Colorred
Ingress protectionIP24D
Temperature range -30°C ... 70°C
Max. wire guage 2.5 sqmm
MaterialABS plastic
Quiescent current260 uA @ 24 V DC (w/o isolator) 360 uA @ 24 V DC (with isolator)
Alarm current6 mA @ 24 V DC
Relative humidity0 ... 95% (non-condensing)